Click to enlarge image
|
Model Number |
ETOS-DNA PLUS Sereis |
Features
- Offers Ethernet 1 port(100baseT/DHCP/Communication Drivers)
- Up to 4 serial communication ports(RS232/ RS422)
- Supports wire(Dedicated Modem) and wireless(CDMA/RF Modem)
- Function to be sending SMS with CDMA Modem(Event Alarm function)
- Various I/O formations(Relay and TR output/ Analog and DC input)
- Possible to use as redundant RTU that is consisted of wire and wireless way
- Controller for controlling and monitoring of unmanned remote sites
Modules
| Classification |
Model |
Specification |
Main (Classify by port) |
ETOS-DNA-PLUS-S20 |
Serial(RS232) 2 ports |
| ETOS-DNA-PLUS-S02 |
Serial(RS422) 2 ports |
| ETOS-DNA-PLUS-S40 |
Serial(RS232) 4 ports |
| ETOS-DNA-PLUS-S04 |
Serial(RS422) 4 ports |
| ETOS-DNA-PLUS-S22 |
Mixed Serial RS232 2 Ports, RS422 2 Ports |
| ETOS-DNA-PLUS-E20 |
Ethernet 1 Port + RS232 2 Ports |
| ETOS-DNA-PLUS-E02 |
Ethernet 1 Port + RS422 2 Ports |
| ETOS-DNA-PLUS-E40 |
Ethernet 1 Port + RS233 4 Ports |
| ETOS-DNA-PLUS-E04 |
Ethernet 1 Port + RS422 4 Ports |
| ETOS-DNA-PLUS-E22 |
Ethernet 1 Port + RS232 2 Ports / RS422 2 Ports |
Option (Classify by I/O) |
DNA-PLUS-OPT-RY16 |
Relay Output 16 Points |
| DNA-PLUS-OPT-TR16 |
TR Output 16 Points |
| DNA-PLUS-OPT-DC16 |
DC24V Input 16 Points |
| DNA-PLUS-OPT-DT15 |
TR output 7 Points / DC 24V Input 8 Points (for combined input and output) |
| DNA-PLUS-OPT-DR16 |
Relay Output 8 Points / DC24V Input 8 Points (for combined input and output) |
| DNA-PLUS-OPT-AD4 |
Analog Input 4 ch |
The methods to classify Main Model name : ETOS-DNA-PLUS-X,Y,Z-AA
- X : Classify Ethernet and Serial : S = Serial, E = Ethernet
- Y : Quantity of RS 232 Ports
- Z : Quantity of RS 422 Ports
- AA : User Memory Size (none, 1M, 2M, 4M)
- ex : ETOS-DNA-E22 = Ethernet 1Port, RS232 2 Ports, RS422 2 Ports, 256kbyte user Memory
Digital Output Specification
| Classification |
DNA-PLUS-OPT-RY16 |
DNA-PLUS-OPT-TR16 |
| Input/ Output Spec. |
Relay Output |
TR Output |
| Input/ Output Points |
16 Points |
16 Points |
| Isolation method |
Relay Isolation |
Photo coupler Isolation |
| Polarity Type |
- |
Sink type(-COM) |
| Rated Load Voltage |
DC24V, AC110V/220V |
DC12V, DC24V |
| Rated Load Current |
5A/COM |
3A/COM |
| Response time |
Off->On |
10 mSecs |
2 mSecs |
| On->Off |
12 mSecs |
2 mSecs |
| Common method |
8 Points / 1 COM |
16 Points / 1 COM |
| Status Display |
Display by LED |
Display by LED |
Digital Input/Output Specification
| Classification |
DNA-PLUS-OPT-DC16 |
DNA-PLUS-OPT-DT15 |
DNA-PLUS-OPT-DR16 |
| Input/ Output Spec. |
DC Input module |
Mixed DC Input/ TR Output |
Mixed DC Input/ Relay Output |
| Input/ Output Points |
Input 16 Points |
Input 8 Points / Output 7 Points |
Input 8 Points / Output 8 Points |
| Isolation method |
Photo coupler Isolation |
Photo coupler Isolation |
Photo coupler Isolation |
| Polarity Type |
Source/Sink (non-Polarity) |
- |
- |
| Rated Load Voltage/ Current |
Input DC24V/11mA |
Refer DC input Module |
Refer DC input Module |
| On Voltage/Current |
Input DC15V/6mA |
- |
- |
| Off Voltage/Current |
Input under DC5V/1mA |
Refer TR Output Module |
Refer Relay Output Module |
| Response time |
Off ->On |
10mSecs |
- |
- |
On ->Off |
10mSecs |
| Common method |
8 Points / 1 COM |
Input 8 Points/1COM Output 7Points/1COM |
Input 8 Points/1COM Output 8Points/1COM |
| Status Display |
Display by LED |
Display by LED |
Display by LED |
Analog Input Specification
| Classification |
DNA-PLUS-OPT-AD4 |
| Input Spec. |
Analog Input Voltage/Current Module |
| Number of Input Channels |
4 Channels |
| Input |
Voltage |
DC -10V~+10V, -5V~+5V, 0~10V, 0~5V, 1~5V |
| Current |
DC 1~20mA, 4~20mA |
| Selecting Voltage/Current |
Selecting by Terminal |
| Digital Output |
-16000 ~ +16000 |
| Resolution |
Voltage |
0.25 mV |
| Current |
1 uA |
| Precision Rate |
± 0.1%(Full Scale) |
| Isolation method |
Isolating Input Terminal and Internal circuits by Photo Coupler(Non-Isolation between channels) |
| Max. Converting Speed |
10mSec / 1 Channel |
| Internal Process |
Average Process(Average Value Setting function), Sampling |
| Status Display |
Display by LED |
ETOS-DNA Analog / Digital Input / Output Wiring Diagram
| 16 Points Relay Output Terminal Wiring |
16 Points TR Output Terminal Wiring |
 |
 |
| 16 Points DC Input Terminal Wiring |
DC 8 Points/Relay 8 Points Mixed Type Terminal Wiring |
 |
 |
| DC 8 Points/TR 7 Points Mixed Type Terminal Wiring |
4 Channel Analog Input Terminal Wiring |
 |
 |
Monitoring Systems about an amount of flowing in unmanned Distributing
Monitoring systems of unmanned constant pressure facilities in City Gas System (Redundancy of wire and wireless)
|
|
|
|
| |
|
|
|